skip to main page
Monitoring

Flow measurement: coolant distributors for data centers

IO-Link flow sensor measures flow and temperature to ensure demand-based chip cooling in the circuit of the coolant distribution units (CDU)

IO-Link, Decentralized Automation, Flow Sensors/Flow Meters

Benefits

  • Precise flow rates for water and glycol mixtures thanks to linearized flow output
  • Minimal impact of fluctuating coolant temperatures thanks to temperature compensation
  • Additional temperature data without the need for an additional measurement point, since the sensor provides both Flow and temperature
  • Flexible installation on pipe sizes ranging from DN15 to DN250 thanks to the immersion principle
  • Decentralized automation via IO-Link Smart Sensor Profiles and IP67 protection rating

Challenge

Data centers are increasingly using direct-to-chip liquid cooling to cool high-density chips: The coolant flows through cooling plates directly to the central processing units (CPUs) and graphics processing units (GPUs) and is circulated via a coolant distribution unit (CDU). The flow determines how quickly heat is dissipated: If the coolant temperature rises, the flow must be precisely increased; if it drops, it must be reduced to save energy. Without monitoring, malfunctions such as air bubbles or cavitation go undetected and compromise cooling performance. What is needed is a measurement solution that records the flow at the inlet and outlet of the cooling lines, as well as before and after the pump, in real time.

Solution

With the FS501 flow sensor, TURCK offers a sensor specifically designed for cooling applications that simultaneously measures flow rate and fluid temperature in CDU cooling circuits. The flow output is linearized for water and water-glycol mixtures and temperature-compensated over the specified medium temperature range, ensuring that fluctuating coolant temperatures have only a minimal effect on the measurement result. In the CDU, one FS501 is installed on both the primary and secondary sides. As an immersion sensor, this model is suitable for many pipe sizes ranging from DN15 to DN250; various screw-in threads allow it to be adapted to the respective cable. The measuring range for water extends up to 3 m/s, and the pressure resistance is up to 300 bar.

The FS501 provides measured values via combined switching and analog outputs (4…20 mA, 0…10 V) or with IO-Link and the Smart Sensor Profile. Via IO-Link, the sensor supports dynamic teach-in and quantity counting via the totalizer function, which simplifies commissioning. Since it is installed directly on the pipeline with IP67 and IP69K protection ratings and transmits its data via IO-Link, it integrates seamlessly into decentralized automation concepts. A rotatable housing that can be rotated up to 340° with a four-digit display, along with high shock and vibration resistance, facilitates on-site use.

The FS501 makes it possible to regulate cooling capacity according to demand, detect malfunctions early, and improve the energy efficiency of chip cooling.

John_Vinesh_large

"With our FS501, cooling system manufacturers can obtain temperature-compensated flow and temperature values from a single measurement point—the foundation for energy-efficient chip cooling tailored to specific needs."

Vinesh John | Product Manager Fluid Sensors | TURCK GmbH